HHSRS VERSION 2
23 (BCC-01)
April 2006
ELECTRICAL HAZARDS
Yes
Yes
No
No
Vulnerable age
Related hazards
Persons aged under 5 years
Fire
Consumer unit in hallway
Power socket in living room
DESCRIPTION OF HAZARDS
Multiple locations
Secondary hazards
Consumer Unit in Kitchen
Consumer Unit in Kitchen
Dwelling:
Pre 1920 ground floor flat
Background: A self contained ground floor flat within a 2 storey block converted into four flats during
the 1970’s. The original property dates back to 1882. The building was constructed on a natural sand
bed in a low lying area and remains subject to the rise and fall of incoming tides. The external wall
construction is of solid stone. The ground floor flat being considered comprises of a kitchen, bathroom,
living room and one bedroom.
A) Living Room: low level consumber unit with missing cover. Two broken double power socket outlets.
B) Kitchen: consumer unit at low level with mising cover and unsealed cable entry points.
LIST OF RELEVANT MATTERS
LIKELIHOOD & OUTCOMES
A
B
a
Out-dated installation
-
-
b
Number and siting of outlets
2
-
c
Fuses and meters
2
2
d
Earthing
-
-
e
Disrepair
3
1
f
Presence of water
-
-
g
Lightning protection
-
-
# Compounding matters
A
B
-
None
-
-
Key
3
Seriously defective
2
Defective
1
Not satisfactory
-
Satisfactory/NA
Likelihood to
1 in
Outcomes to
0.5 10.0 43.1 46.4
%
5600
A B C D E
F G H
I
Replace the broken sockets, resite the consumer units at a higher level (providing
covers or enclosing in boxing) and sealing the cable entry points would reduce
the likelihood of an occurrence to the average.
Av:2
IMPROVE
Justification
NEW RATING
Av: Nos
Average likelihood, outcomes and HHSRS score by persons aged under 5 years in all
dwellings,1997-99.
Score:
5
J
23 (BCC-01)
April 2006
HEALTH AND SAFETY RATING SYSTEM SCORES
LIKELIHOOD
Low
High
1 in
10
7.5
4
Av: All dwellings
< 4200 2400 1300 750 420 240 130
75
42
24
13
10
2.5
1.5 >
Justification
OUTCOMES
Class I
Class II
Class III
Class IV
Justification
RATING
Two low-level broken sockets in the living room the exposed wiring of which is
easily accessible to young children. In addition there are two low-level consumer
units with missing covers, the one in the kitchen also has unsealed cable entry
points, and the cables may be reached by children
%
Av all dwellings: 0.6
0.5
< 0.05 0.15 0.3
0.7
1.5
3
7
15
26
38 >
Av: 8.2
10
< 0.05 0.15 0.3
0.7
1.5
3
7
15
26
38 >
Av: 49.2
43.1
< 0.05 0.15 0.3
0.7
1.5
3
7
15
26
38 >
Av: 42.0
46.4
< 0.05 0.15 0.3
0.7
1.5
3
7
15
26
38 >
As the earthing is satisfactory, there are no other factors that would indicate the
harm outcomes would be different from the national average spread of harms
(Class III being the most probable).
Av. All dwellings: 2
C D E
F G H
I
J
A
B
Score:
2839
RATING SCORES AFTER IMPROVEMENT