# Compounding matters
HHSRS 08/06
Yes
Yes
No
No
Lighting
Vulnerable age
Related hazards
Persons of all ages
None
Inside bedsit showing part
of the single window
DESCRIPTION OF HAZARDS
DWELLING:
Front elevation
Steps leading to basement
as viewed from the
property
Basement bedsit in a 3 storey +
basement semi detached house
Background: The house is of traditional brick construction with slate covered roof built in 1947. It contains
seven bedsits in total. There are two shared bathrooms, one on the ground floor and the other at first floor
level. The ground floor kitchen is shared.
The Basement Bedsit: The bedsit is approached via a set of stone steps at the front of the house. Inside the
only window to the bedsit is sited just below the ceiling and to the right of the entrance door to the bedsit. It
has no openable area and measures 750mm by 350mm. There is virtually no natural light in the bedsit, and
artificial lighting is required for basic domestic activities. There is no outlook.
LIST OF RELEVANT MATTERS
LIKELIHOOD & OUTCOMES
a
Obstruction
1
b
Size, shape and position of the window
3
c
Position of artificial lighting
-
d
Control of artificial lighting
-
e
Glare etc
-
f
Window view
3
g
Outlook
3
13 (IDeA - 01)
August 2006
Multiple locations
Secondary hazards
A
B
-
None
-
-
Key
3
Seriously defective
2
Defective
1
Not satisfactory
-
Satisfactory/NA
13 (IDeA - 01)
August 2006
HEALTH AND SAFETY RATING SYSTEM SCORES
LIKELIHOOD
Low
High
1 in 2
Av: All Dwellings: 50,825
2
< 4200 2400 1300 750 420 240 130
75
42
24
13
7.5
4
2.5
1.5 >
Justification
The natural lighting is wholly inadequate and the outlook very limited. Normal domestic
activities could only be carried out under artificial light throughout the year. It is highly likely
that the occupier would suffer some psychological harm from living in the dwelling for a
year or more with such a poor outlook and with limited natural light. Those matters justify a
major increase in likelihood to near certainty.
OUTCOMES
%
Av: All Dwellings: 0.1
Class I
0.1
< 0.05 0.15 0.3
0.7
1.5
3
7
15
26
38 >
Av: 0.9
Class II
1
< 0.05 0.15 0.3
0.7
1.5
3
7
15
26
38 >
Av: 9.0
Class III
10
< 0.05 0.15 0.3
0.7
1.5
3
7
15
26
38 >
Av: 90.0
Class IV
88.9
< 0.05 0.15 0.3
0.7
1.5
3
7
15
26
38 >
Justification
There are no obvious factors justifying a change in the spread of harms from the national
average.
Av. All Dwellings: 0
RATING
A
B
C
D
E
F
G
H
I
J
Score:
2945
RATING SCORES AFTER IMPROVEMENT
IMPROVE
Likelihood to
1 in
320
Outcomes to
0.1
1.0 10.0 88.9
%
Justification
To continue in use as a habitable room additional window(s) should be installed (if
physically possible) sufficient to allow domestic activity to be carried out in daylight hours
without the need for artificial lighting. However as a basement bedsit the situation will
remain inherently worse than average mainly because of the limited outlook.
Av: 0
NEW RATING
A
B
C
D
E
F
G
H
I+
J
Score:
18
Av: Nos
Average likelihood and health outcomes for persons of all ages.